AIR 100 kA 240 V AC 50/60 Hz UL 489AIR 65 kA 480 V AC 50/60 Hz UL 489AIR 25 kA 600 V AC 50/60 Hz UL 489Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage
600 V AC 50/60 Hz UL 489
Network Frequency
50/60 Hz
[Ics] rated service breaking capacity
35 kA 240 V AC 50/60 Hz IEC 60947-225 kA 380/415 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
8 kV IEC 60947-2
trip unit technology
Electronic, basic, ET 1.0,
magnetic tripping current
1000…5000 A
continuous current rating
80 %
[Ui] rated insulation voltage
750 V IEC 60947-2
trip unit name
ET 1.0
suitability for isolation
Yes IEC 60947-2
utilisation category
Category A
AWG gauge
3 x AWG 3/0…3 x 500 kcmil aluminium/copper
local signalling
1 trip indicator green)
mounting mode
Unit mount lug)
Mounting Support
Lug
electrical connection
Lugs loadLugs line
terminal identifier
AL800M23K
long time pick-up adjustment range
300…800 A
tightening torque
442.54 lbf.in (50 N.m) 0.15…0.37 in² (95…240 mm²) (3 x AWG 3/0…3 x 500 kcmil)
number of slots
2 auxiliary switch OF plug-in)1 alarm switch SD plug-in)1 voltage release MN or MX plug-in)
Power wire stripping length
0.98 in (25 mm)
Color
Black
Height
12.86 in (326.64 mm)
Width
8.27 in (210.06 mm)
Depth
8.05 in (204.47 mm)
Net Weight
29 lb(US) (13.15 kg)
Quantity per Set
1
Environment
quality labels
CE
standards
ULCSANEMANOM-003-SCFI-2000IEC 60947-2
product certifications
ULCSANOM
IP degree of protection
IP40
pollution degree
3 IEC 60947-1
Ambient Air Temperature for Operation
-13…158 °F (-25…70 °C)
Ambient Air Temperature for Storage
-58…185 °F (-50…85 °C)
operating altitude
< 6561.68 ft (2000 m) without derating13123.36 ft (4000 m) with derating
Aún no hay valoraciones.